GFS Power Space Critical Power Solutions 18 - 111Amp Systems |
Incredible Functionality,
Flexibility, and Scalability in a 2 RU, 1.0 to 6.0 Kw DC Power System
Features:
Specifications: Centurion II
Voltage Range: 90-300V (derate @ 115 input) Frequency Range: 45-65 Hz Power Factor: >0.99 Efficiency: >94% (from 30-95% output power) DC Output
Polarity: Positive earth. 48 volt, negative earth 24 volt
DC Distribution: Load: 16 breaker position capacity, available amperages (specify) 6A, 10A, 20A, 30 amp, with tripped breaker alarm Battery: 2 x 100A battery circuit breakers. Breaker Fail Detection: Electronic fail detection on both load and battery. Breakers Low Voltage Battery Disconnect: 125A battery LVD installed standard, with disconnect alarm Monitoring & Control: Monitors all power system conditions including DC voltage, rectifier current, battery current, battery temperature, and distribution failure. Visual notification of alarm conditions by LED's and a 4 line x 16 character alpha numeric display mounted on the front panel, with remote notification being enabled by relay contacts, RS232 or TCP/IP (using SNMP). It has a built-in web based configurator allowing setup of system parameters using a web browser and utilizes a USB communications port which allows for local monitoring of system operations as well as easy downloading of configuration files for multiple site installations. General System Protection: Current Limit: Adjustable to 50-100% of maximum rated current. Over Temperature: Automatic current reduction, backup shutdown protection. Polarity Reversal: Output fuse with crowbar diode. Over Voltage: Adjustable limit. Input Voltage: Auto shutdown, auto restart when correct voltage restored. Input Inrush: <2x maximum input current. Input Fuses: In phase and neutral. Technical Characteristics: Noise: Ripple <100Hz: <1mV rms unweighted Voice band 100Hz-5KHz: <1mV rms psophometric Wide band 5kHz-1MHz: <5mV rms unweighted Peak to Peak 0-20MHz: <100mV peak to peak Isolation: Input to Output: 4000V DC Input to Chassis: 3500V DC (VDR to chassis removed) Output to Chassis: 2100V DC Regulation: Line = ±0.1%, Load = ±0.5% (no load to full load) Mechanical: Shelf: Dimensions 19" W x 3.5" H x 15.35" D (19" x 2U x 389.89mm) Weight: 19.84 Lbs (9.01kg) excluding rectifier modules Rectifiers: Dimensions 4.25" W x 2.75" W x 11.1" D (107.95mm x 69.85mm x 281.94mm) Weight: 3.15 Lbs (1.43kg) Cooling: Forced cooled Environmental Ambient Temperature: Nominal: 25+/-5º C Range: -10º C to +70º C (maximum output power is derated above +50º C) Humidity: 5-95% RH (non-condensing) Altitude: <8,202 ft., De-rate maximum ambient temperature by 4º C per 3,280 ft. above sea level. Compliances: Safety: EN60950 Electrostatic Discharge: CISPR24 Radiated Radio Freq: CISPR22 AC Harmonics: EN61000-3-2 AC Flicker & Fluctuation: EN61000-3-3 Other: CE & RoHS compliant
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
For pricing and availability please email : sales@gfspower.com.auShould you have a requirement that cannot be met from the current Web site please email us @ sales@gfspower.com.auReseller inquiries are welcome, please email: raymond@gfspower.com.au Last modified: 16-Aug-2011Webmaster: raymond@gfspower.com.au
|