GFS Power

Space Critical Power Solutions

  DC Disconnects

 Home

 

 

Rack Mount LVD PFM-400
 
Features
 
• Automatic low voltage battery disconnect protects batteries in the event of extended AC power loss
• Manual battery disconnect switch allows service/replacement of batteries without system shutdown
• 400 amp rating
• 12, 24 or 48 VDC input/output
• Use with positive, negative or floating ground
• Status lights indicate system and battery connect/disconnect status, assisting technicians in system troubleshooting
• Summary alarm contacts (form C) allow remote indication of system status
• Separate high amp ground bus provided
Additional Power Management Features
 
• High current bus provides parallel tie point for multiple rectifiers
• Digital volt/amp meter
• Summary alarm contacts (form C) allow remote indication of system status
• Up to five optional isolated distribution circuit breakers with "TRIP" alarm contacts
 
Specifications
 
Factory set actuation voltages:
12 VDC 24 VDC 48 VDC
Connect 12.4 24.8 50.0
Disconnect 10.4 20.0 40.0
• Min/Max Connect/Disconnect Voltages User adjustable ± 15%
• Max continuous current: 400 amps
 
Mechanical/General
• Heavy duty plated copper bus bar
• Anodized aluminum front/side panels
• 19" or 23", flush or 6" forward rackmount
• Dimensions: 3.5" H x 17" W x 20.5" D
• Weight: 20 lbs, 9.1 Kg.
 

Data Sheet

Technical Sheet

Low Voltage Disconnect-LVD

Discharging batteries beyond a critical low voltage can damage the batteries and/or load, and require a longer recharge interval. A low voltage disconnect prevents this condition. The LVD contains a sense and control circuit housed in a compact, rugged, vinyl-clad aluminum case. It is installed in-line between the battery and the load. The unit continually monitors battery voltage and if it falls below a preset voltage threshold, the load is automatically disconnected. When batteries are recharged past another pre-set voltage the load is reconnected. connect and disconnect points are user adjustable.

LVD Series Voltage Contact Current Rating Ground Style
Low Voltage Disconnect 12V 30Amp Negative External
Low Voltage Disconnect 12V 75Amp Negative External
Low Voltage Disconnect 24V 50Amp Negative External
Low Voltage Disconnect 48V 30Amp Positive External

 

 