The DPS 600B-48-4 19IN power supply system is designed for
various applications such as digital access, wireless base stations, microwave
links as well as PABX. Numerous options provide solutions for global
applications in different environments. The integrated modular power system
allows flexible adaptations. It contains up to 4 rectifiers DPR 600B-48 or DPR
300B-48, AC- and DC-connections, battery connection and power system controller.
These features together with the very short depth are the key factors for the
success of this power system, offering cost-effective and reliable solutions.
This compact and high density power supply system is the perfect choice for
space-critical locations.
Features
-
19” / 2U shelf power
system up to 2400 W
-
High power density
-
Very short depth
-
Fits into 300 mm deep
ETSI cabinets
-
Fan cooled rectifiers
DPR 600B-48 or DPR 300B-48
-
Integrated power
distribution
-
Easy installation
-
Dimensions (h x w x
d) 88.9 x 430 x 280 mm
Applications
-
Digital subscriber
line (DSL)
-
Fiber in the loop
-
Transmission
-
PBX
-
Network components
Technical Specifications
Download Data Sheet: 5 - 20Amp DC Power Systems
|
General |
|
Efficiency |
≥
92 % (DPR 600B-48)
≥ 91.5 % (DPR 300B-48)
|
|
EMI, radiated |
EN 55 022, class B |
|
Safety |
EN 60 950, class I |
|
Cooling |
Fan cooled rectifiers |
|
Protection |
IP 20 |
|
Input |
|
AC connection |
1 x L / N / PE |
|
Nominal voltage |
230 Vrms |
|
Voltage range |
80 ... 300 Vrms |
|
Range, reduced power |
80 … 130 Vrms (DPR 600B-48) |
|
Frequency range |
50 / 60 Hz |
|
Current nominal |
11.6
Arms (DPR
600B-48)
5.9 Arms (DPR
300B-48)
|
|
Current maximum |
24 Arms (DPR
600B-48)
12 Arms (DPR
300B-48)
|
|
Line current |
Meets IEC 1000-3-2 |
|
Mains terminal |
Screw terminal 6mm² |
|
Transient OVP |
Option / external |
|
Output DPR 600B-48 DPR 300B-48 |
|
Voltage, nominal |
-53.5
Vdc |
|
Voltage range |
-42 …-58 Vdc
|
|
Output current |
44.8 Adc |
22.4 Adc |
|
Current limitation |
56 Adc |
28 Adc |
|
Power, limitation |
4 x 600 W |
4 x 300 W |
|
Power, nominal |
2400 W |
1200 W |
|
Power, redundant |
1800 W |
900 W |
|
Power, at 88Vrms |
1600 W |
1200 W |
|
Load distribution |
|
Fuses (DIN 72581-3) |
8x 10A +
8x 20A (standard) |
|
Load terminals |
Screw terminal 4mm² |
|
PLD |
None |
|
Battery connection |
|
Fuses (DIN 72581-3) |
2 pieces / 50 A |
|
Battery terminals |
Screw terminal 16mm² |
|
LVD |
Included |
| Strengthening
terminal |
1 Screw terminal
16mm² (+0V) |
|
Mechanics
|
|
Construction |
Steel rack |
|
Cabinet standard |
IEC 297
(19 INCH)
ETS 300 119-3 (with
included
alternative brackets )
|
|
Width, body |
430 mm
(screws not included) |
|
Depth, overall
|
282 mm
(including handles) |
|
Height, overall |
88 mm
(2 U) |
|
Weight, system |
7 kg / 15
lb (excluding rectifier) |
|
Weight, rectifier |
0.9 kg
/ 2.0 lb |
|
Environment |
|
Operation temperature |
-25
… +65 °C |
|
Relative humidity |
95 %
max, non condensing |
|
Control and monitoring
|
|
Power system controller |
PSC 1 (included) |
|
Battery temperature |
Sensor with 2,5m cable (incl.) |
|
See leaflet for power
system controller |
|
Available Options |
|
Number of rectifiers |
1…4 x DPR 600B or DPR 300B |
|
Additional dist. Fuses |
1…20A (DIN 72581-3) |
|
Alt. AC selectivity fuses |
2 x 4 A (5 x 20 mm) |
|
Transient OVP |
For
external installation |
|
Rectifier slot cover |
D0117507 |
|
Digital User manual |
Available as PDF at request |
|
Communication kit
|
D0118739 (software & cable) |
|
Communication cable |
D0103915 (cable only) |
|
Agent 1000B
(SNMP & Web interface
hardware kit for PSC1)
|
D0119968
(MIB & SNMP setup
software
+ digital manual,
available at
request on CD-ROM)
|
|
Included Accessories |
|
ETSI mounting
|
2 pc 88mm
brackets |
|
User manual (on paper) |
In
English language |
Subject to change due to
technical progress.
|