48V DC 24V DC or 12V DC
19/23" Rack-mount
Combination DC Power Distribution Panel
Incorporates GMT Fuses and Circuit Breakers
|

DST-FB
- Combination DC Power Distribution Panel Incorporates
GMT Fuses and Circuit Breakers
The DST-FB panel offers a
unique combination of circuit protection, utilizing both circuit breakers and
GMT fuses in a single, 2 RU rack mount assembly. This provides integrators a
flexible DC power distribution system allowing the installer to assign low power
loads to fuses and high power loads, up to 30 amps, to circuit breaker protected
circuits. The unit features dual busses, one bus accommodating 8 plug-in circuit
breakers and the second holding up to 8 GMT style fuses. Front panel LEDs
indicate power available per bus as well as blown fuse and tripped/off circuit
breaker occurrence. Tripped condition also activates form C contacts for
integrating remote alarm reporting. The panel integrates with 12, 24 or 48 volt
systems, any ground reference, making the unit ideal for any power system.
Features
12, 24, or -48 VDC,
Positive or Negative Ground
Integrates easily with any power system
Dual Bus (100 amps ea.): Bus A, 8 x GMT fuses; Bus B, 8 x plug-in circuit
breaker capacity
Indicators: Power available LED, blown fuse LED, tripped/off circuit breaker
LED
Form C alarm contacts
Electrical
Nominal Input: 12, 24 or 48
VDC, Positive or Negative ground
Total Circuit
Capacity (16 total): 8 GMT fuses & 8
breakers
Dual Bus:
Bus rating - 100 Amps each max.
Bus A: Feeds 8 x GMT fuses, 15 Amps max., fuse
rating
Bus B: Feeds 8 x plug-in circuit breakers, 30
Amps max., breaker rating
Circuit Breaker
Values: 5, 10, 15, 20, 25 & 30 amp., easy plug-in
via panel front (sold separately)
GMT Fuse Values:
1, 3, 5, 7.5, 10 & 15 amp, (sold separately)
Indicators & Alarms
Power Available LED, one per Bus (Green)
Blown fuse LED (Red)
Tripped/Off circuit breaker LED (Red)
Alarm Contacts: Form C, one each for Bus
A & Bus B, activates on any of the above alarm conditions
Mechanical
Chassis: Vinyl laminated
aluminium with powder coated front panel
Rack Size: 19" or 23", 2 RU, flush or
centre mount
Dimensions: 3.5" H x 19/23" W x 11" D
Weight: 5.5 Lbs. with no breakers
installed
Environmental
Operating Temperature: -40 to
+60°C

8 Plug-in Circuit Breaker Capacity 8 GMT Fuse Capacity
|