Centurion - Medium Power - 550 Watts/Rectifiers

Newmar’s Powering the Network Centurion Rectifier System comprises a low profile 3.5” (2 RU) shelf which accommodates up to three 550 watt, -48 or +24 volt hot-swap rectifiers, plus a voltage control and alarm module. The system is scalable/adaptable for N, N+1 or N+2 configurations. Centurion Rectifier System is ideal for powering network transmitters. Front panel test points and system voltage adjustment pot are provided for fine-tuning output to the requirements of sensitive loads, charging batteries, and to optimize load sharing between Centurion Rectifier shelves. Relay contacts for output ok. Forced air cooling of rectifier extends components life.

 

The Centurion Rectifier System comprises a low profile 3.5” (2 RU) shelf which accommodates up to three 550 watt, -48 or +24 volt hot-swap rectifiers, plus a voltage control and alarm module. The system is scalable/adaptable for N, N+1 or N+2 configurations. And is ideal for powering network transmitters.

Front panel test points and system voltage adjustment pot are provided for fine-tuning output to the requirements of sensitive loads, charging batteries, and to optimize load sharing between Centurion Rectifier shelves.

Local and remote monitoring is provided by alarm contacts which report system off, as well as major and minor rectifier conditions via alarm contacts and front panel warning LEDs. Integrate SNMP monitoring with Site Power Monitor. Engineered for compatibility with NEWMAR’s PFM-400, Power Function Manager to create an integrated power system with metering, alarms, low voltage disconnect and distribution circuit breakers

Centurion Rectifier Systems

Shelf
Input
Capacity
Size
Weight
CRS-48 115/230 VAC Nom.
3 Unity Rectifiers (-48 V)
1 Voltage Control and Alarm Module
19/23” Rackmount, 2 RU
10 lbs/4.5kg
CRS-24
115/230 VAC Nom.
3 Unity Rectifiers (+24 V)
1 Voltage Control and Alarm Module
19/23” Rackmount, 2 RU
10 lbs/4.5kg
 
Rectifiers
Input Amps @ Full
Load 115/230V
Output Voltage
Output
Amps Cont.
Watts
Size
Weight
CR48-10
6/3
-54.4 VDC, adjustable 50-59 VDC
10
550
2 RU
6 lbs/2.5kg
CR24-20
6/3
+27.2 VDC, adjustable 25-29.4 VDC
20
550
2 RU
6 lbs/2.5kg

Features

  • 550 watt rectifier units, 48 or 24 volt, slide and lock into the Centurion Shelf
  • Shelf accommodates up to three rectifiers—1650 watts total
  • Scalable/adaptable hot swap configuration: N, N+1, N+2
  • Front panel status indicators, output voltage test points and voltage adjustment
  • Alarm Relay contacts for output OK, minor and major alarms
  • Forced air cooling of rectifiers extends component life
  • 115/230 VAC shelf/rectifier input— easily adapts to available site power
  • Shelf adapts for 19” or 23” rack; centre or flush mount (four-point cabinet mount optional)

Download Data Sheet - Centurion Rectifier Systems

Download Manual - Centurion Rectifier Systems

Rectifier Specifications
Models: CR48-10, CR24-20
Input Voltage/Frequency: 85-264 VAC* / 47-63 Hz.
Input Amperage: 6 amps @ 115V and full load, 3 amps @ 230V and full load
Power Factor: .96-.98
Output Voltage/Amperage:
    CR48-10:
-54.4 VDC, adjustable 50-59 VDC, 10 amps continuous
    CR24-20: +27.2 VDC, adjustable 25-29.4 VDC, 20 amps continuous
    * 100 % output power available from 105 to 264 VAC; Derate output linearly from 100% @ 105 VAC to 80% @ 85 VAC
Regulation: +/- 2 %
Ripple: CR24-20: 150 mV, CR48-10: 250 mV
Protection: Over-voltage, current limiting, over-temp, forced air cooling, input and output fuses
Indicators: Front panel LED indications: “DC OK/DC FAIL”
Operating Temperature: -10°C to +60°C; 100% load from 0°C to +50°C; Derate linearly to 80% load from +50°C to +60°C and 0°C to -10°C
Weight: 6.0 lbs., 2.5kg
Designed to: EN55022 Class A, EN61000-4-2,3,4,5,6,8,11, EN61000-3-2,3
Approvals:
UL 1950, CE

Rectifier Shelf Specifications
Model: CRS-48/CRS-24
Input: 115/230 VAC nominal, 47-63Hz.
Capacity: Up to Three Centurion Rectifiers, -48 or +24 volt Front panel voltage test points and system single point voltage adjustment

Alarms/Indicators:
• Output OK (Form A)
• Minor Alarm (Form C)
• Major Alarm (Form C)
• Battery Over-Temperature (with optional sensor)
• 10 segment LED output current bar graph

Size/Wt.: 3.5" H x 17.15" W x 21.5" D/10 Lbs.

Mounting: With 19” or 23” rack; centre or flush mount/adapters

Options

• PFM-400, Power Function Manager creates a fully integrated power system with Metering, alarms, low voltage   disconnect, and distribution circuit breakers.

 

 