GFS Power Space Critical Power Solutions Enclosure Power Sys |
Features:
12/24 VDC Power, 150
watts
Designed specifically for
back plane or din rail mount in NEMA enclosures
Simultaneously powers
load and maintains back up battery
Rated for extreme
temperature operation -20° to 60° C (-40° F to 140° F)
Temperature compensated
output, prolongs battery life
Alarm contacts and low
voltage disconnect built in
The Enclosure Power System
is designed specifically for outdoor cabinet applications which typically
include back up batteries. The environmentally hardened power circuitry
provides 12 or 24 volts to the load and maintains the back-up batteries. A
sense circuit adjusts charge voltage based on temperature ensuring batteries
are properly maintained no matter the climate.
A low voltage disconnect
circuit removes the load from the batteries after an extended power outage,
thus preventing total discharge and allowing rapid replenishment when AC is
restored. There are also alarm contacts that can be user configured to
monitor several vital functions of the system and relay information to base
station that service is needed.
The low profile rugged
anodized aluminum case is designed for enclosure mount, either on back plane
or din rail. Front panel terminals for AC input, battery and load provide
easy wiring access.
Specifications
Typical pole mount application with Enclosure Power System, battery and transmitter.
|
For pricing and availability please email : sales@gfspower.com.auShould you have a requirement that cannot be met from the current Web site please email us @ sales@gfspower.com.auReseller inquiries are welcome, please email: raymond@gfspower.com.au Last modified: 16-Aug-2011Webmaster: raymond@gfspower.com.au
|