GFS Power

Space Critical Power Solutions

  Power Modules

 Home

 
12V DC    24V DC    and    48V DC  
Positive    Negative    or    Floating ground
 
These Versatile Rectifier Modules function as either power supplies or battery chargers for 12, 24 or 48 volt systems; positive, negative or floating ground. They may be employed singly or in combination, enabling the installer to scale the system anywhere from 500 to 10,000 watts per rack. Units may be paralleled for N + 1 redundancy and alarm contacts allow local or remote monitoring. An optional DC quick connect wiring kit allows easy replacement of modules without system shutdown.
 
 
 
 
 
 
Power Modules may be used separately as a power source, or they may be integrated with the Power Function Manager to greatly expand the system capability with other functions such as digital output monitoring, powering multiple loads via circuit breaker distribution and low voltage battery disconnect.
 
 
 
 
 
 
 
 
 
Features
  • 12, 24 or 48 volts output; pos., neg. or floating ground
  • 115 or 230 VAC, 50-60 Hz input 560 & 1000 watt models
  • 230 VAC only 2200 watt model
  • 560, 1000 or 2200 watts per module (approx.)
  • Built-in oring diode for parallel or N + 1 configuration
  • Power supply or battery charger operation (DC UPS system)
  • Battery charging options: three-step charging, gel/lead-acid switch, equalization and temperature compensation
  • Remote shutdown control option via TTL signal (except 2200watt models)
  • Form C alarm contacts
  • 19" or 23", 2 RU, flush or 6” forward rack-mount
Models
 
Power
Modules
Input Amps
@ Full Load
115/230V
Output
Watts
Weight
VDC
V Out
VDC
V2
Amps
Cont.+
Lbs.
Kg.
PM-12-40
8.5/4.3
13.6
14.3
40
560
12.2
5.5
PM-12-70
16/8
13.6
14.3
70
1000
15.2
6.9
PM-24-20
8.5/4.3
27.2
27.9
20
560
12.2
5.5
PM-24-35
16/8
27.2
27.9
35
1000
15.2
6.9
PM-48-10
8.5/4.3
54.4
55.1
10
560
12.2
5.5
PM-48-18
16/8
54.4
55.1
18
1000
14.0
6.4
PM-48-50
*/22
54.4
50
2200
34
15
VDC (V out) Measured at output terminal with oring diode
VDC (V2) Measured at direct output terminal
+ For parallel configuration/load sharing derate output 10%
* 230 VAC input only
** in development
 
Mechanical/General
  • Anodized aluminum front panel
  • Vinyl laminated base and cover
  • 19" or 23" Rackmount, brackets provided
  • Wall-mount via optional brackets
  • IEC AC entry module. 6’ power cord with NEMA 5-15 plug, 115 VAC.(560 watt models)
  • 6’ power cord with NEMA 6-15 plug, 230 VAC (1,000 watt models)
  • 6’ power cord with NEMA 5-20 plug, 115VAC also supplied (1,000 watt models)
  • Hardwire junction box on 2200 watt units, no power cord provided
  • 1/4” -20 Output stud (560 watt models)
  • Output bus bar (1,000 & 2200 watt models) with 1/4” - 20 studs
  • Output "OK" L.E.D.
  • Loss-of-output alarm contacts- Form C, plus loss of AC alarm contacts Form C (2200 watt units only)
  • Front panel voltage test points
Performance Specifications
 
Download Data Sheet - Power Modules
 
Download Manual - Power Modules
  • Input: 85-135/170-270 VAC (selectable), 47-63 Hz. 560 & 1000 watt models. 207-253 VAC only 2200 watt models
  • Power Factor: 0.7
  • Regulation: ± 1% at direct output (V2); ± 2% through "oring" diode (V out)
  • Ripple: 1% (Typical)
  • Efficiency: 80-85% @ full load
  • Front panel Output Voltage adjustment pot range: ±10%
  • Altitude Range: Full output to 5,000 feet. Derate output current 4% per 1,000 feet to 10,000 feet max.
Design Standards
  • UL 1950 / EN 60950 (Safety)
  • EN 50082 (Immunity)
  • EN 55014 (Conducted)
Options
  • Three stage charger function with gel/lead-acid selector Model: CFB 560 & 1000 watt units only
  • Temperature compensation (for battery charging). All models.
  • DC quick connect wiring kit, 560 & 1000 watt Models: QCK-3 (for 2-3 unit PM system), QCK-6 (for 4-6 unit PM system), CCK-4 (2200 watt models)
  • “Universal” mounting bracket; Model: UMB-PM (500 & 1KW models only)
  • Metering, alarms, LVD and distribution breakers (PFM-400 option)
Temperature Rating
560 & 1000 watt models: -40° C to +60° C; Derate linearly from 100% load @ 50°C to 75% @ 60° C
2200 watt models: 0-50°C
 
 
 